12.13 Transient Phasor Recorder (TPR)
170
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
12.13.3 Binary Triggers
All binary inputs of VCDAUs, VDAUs, CDAUs, DDAUs and BDAUs modules can be used as
binary trigger values.
Figure 12-34 TPR, Binary Trigger tab
Select the channel from the drop-down menu of the
Channel
box.
The
Channel description
and the
Abbreviation
that you have parameterized before are
displayed in the parameter box of the channel.
Activate or deactivate the
Retrigger Blocking
by clicking the appropriate radio button.
Activate the checkboxes
Change to normal state
and/or
Change to alarm state
.
Note
Change to alarm state
means: A normally open contact (connected to an input parameterized
as normally open contact) is closed or a normally closed contact (connected to an input param-
eterized as normally closed contact) is opened.
Change to normal state
means: A normally open contact (connected to an input parameterized
as normally open contact) returns to open or a normally closed contact (connected to an input
parameterized as normally closed contact) returns to closed.
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...