16
16.1 Technical Data of the SIMEAS R-PMU
243
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Power failure bridging
- without battery
- with battery
Power failure bridging
over 10 minutes if all functions are in operation
and the battery is fully charged
Power input
ZE 8/16
8 analog / 16 binary channels
DC 24 V to DC 60 V
20 W
DC 110 V to DC 250 V
18 W
AC 115 V to AC 230 V
30 VA
ZE 32/64
32 analog / 64 binary channels
DC 24 V to DC 60 V
45 W
DC 110 V to DC 250 V
40 W
AC 115 V to AC 230 V
70 VA
Table 16-1
Power failure bridging times acc. to IEC 60255-11/1979 and VDE 0435 part 303/
09.84
Power failure bridging time
ZE 8/16
ZE 32/64
for DC 24 V
≥
400 ms
≥
150 ms
for DC 60 V
≥
450 ms
≥
170 ms
for DC 110 V
≥
500 ms
≥
180 ms
for DC 250 V
≥
700 ms
≥
200 ms
for AC 115 V
≥
500 ms
≥
200 ms
for AC 230 V
≥
800 ms
≥
350 ms