18
18.2 Data Acquisition Units (DAU)
266
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
With
binary signals
, the sampling frequency for all DAU types is consistently 2 000 Hz.
Frequency accuracy at f
n
±5 Hz
VCDAU:
5 mHz
VDAU:
5 mHz
CDAU:
5 mHz
Table 18-9
Sampling frequency
DAU type
Rated
frequency
Frequency
range
Sampling
frequency
Sample values
per period
VCDAU; VDAU; CDAU
50 Hz
25 Hz to 60 Hz
9,600 Hz
192
DDAU
50 Hz
0 Hz to 500 Hz
VCDAU; VDAU; CDAU
60 Hz
30 Hz to 70 Hz
11,520 Hz
DDAU
60 Hz
0 Hz to 500 Hz
Summary of Contents for SIMEAS R-PMU