6
6.3 Calculating Derived Values
49
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Delta connection: phase-to-phase voltages and currents
With
and :
Positive-sequence system:
Negative-sequence system:
a
e
j
2
Π
3
⁄
(
)
=
a
2
e
j
2
–
Π
3
⁄
(
)
=
V
1
V
L12
a
2
V
L23
⋅
–
3
----------------------------------------
=
I
1
1
3
---
I
L1
a I
L2
a
2
I
L3
⋅
+
⋅
+
(
)
⋅
=
V
2
V
L12
a V
L23
⋅
–
3
-------------------------------------
=
I
2
1
3
---
I
L1
a
2
I
L2
a I
L3
⋅
+
⋅
+
(
)
⋅
=
Note
Only the absolute value of the symmetrical components is recorded.
Note
The Continuous RMS-value Recorder (CRR) only records the absolute value of the
symmetrical components.
Triggering is also done using only the absolute value of the symmetrical components.
The PMU transfers the positive-sequence system as complex values!