3 System Messages
282
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
640
0
PARSER
System parameter file fault
Hotline, install SIMEAS R-PMU firmware or
OSCOP P update
641
0
PARSER
Fault: System parameter file not available
Hotline
642
0
PARSER
Unsupported V30.xx parameters
After a firmware upgrade there are still
V30.xx parameters on the device, you have
to parameterize the device (overwriting the
old parameters).
643
0
PARSER
Fault: Unknown system parameter file
version
Hotline
644
0
PARSER
Slot parameter file fault
Hotline, install SIMEAS R-PMU firmware or
OSCOP P update
645
0
PARSER
Fault: Slot parameter file not available
Hotline
646
2
PARSER
Slot parameter check OK
-
647
2
PARSER
System parameter check OK
-
769
0
PRINTER Printer not connected
-
770
0
PRINTER Printer switched off
-
771
2
PRINTER Printer not ready
-
772
0
PRINTER No printer paper
-
774
0
PRINTER Printer queue: Can not open fault record.
File number:
Unable to print a fault record:
The file is damaged or deleted in ring buffer
mode.
1056
0
DAU
Incomplete TAR recording. File number:
TAR record cannot be used due to
inconsistent DAU data.
1057
0
DAU
Incomplete TPR recording. File number:
TPR record cannot be used due to
inconsistent DAU data.
1059
0
DATABAS
E
Fault writing into the database.
Recorder type:
Hotline
1060
0
DATABAS
E
Database access fault.
Recorder type:
Hotline
1061
0
DAU
Wrong data block ID.
Recorder type:
TAR/TPR record cannot be used due to
inconsistent DAU data.
1062
0
DATABAS
E
Fault in message queue.
Recorder type:
Hotline
1063
0
DATABAS
E
Could not copy recording. Recorder type:
Hotline
1064
0
DATABAS
E
Could not create database. Recorder type:
Hotline
1065
1
DATABAS
E
Deleting recordings. Recorder type:
-
1066
1
DATABAS
E
Log recorder created
Log recorder created due to a firmware
upgrade.
1067
0
DATABAS
E
Database overflow, recorder type:
Hotline
1068
1
DATABAS
E
Database initialized, recorder type:
A new database created due to new
parameterization or a firmware upgrade.
1069
1
DATABAS
E
Deleting recordings.
Recorder type:
-
1070
1
DATABAS
E
Database initialized. Recorder type:
A new database created due to new
parameterization or a firmware upgrade.
1071
0
DATABAS
E
TAR recording deleted. File number:
TAR record cannot be used due to
inconsistent DAU data.
1072
0
DATABAS
E
TPR recording deleted. File number:
TPR record cannot be used due to
inconsistent DAU data.
1281
2
CALL_PC Callback PC started. Interface:
-
Log No.
Type
Class
Description
Comment
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...