16
16.1 Technical Data of the SIMEAS R-PMU
242
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
16.1
Technical Data of the SIMEAS R-PMU
16.1.1 Construction
ZE 8/16
Dimensions (W x H x D)
223 mm x 266 mm x 300 mm
Number of slots
3
Slot 1:
CPU
Slot 2:
DAU
Slot 3:
Power supply unit
ZE 32/64
Dimensions (W x H x D)
445 mm x 266 mm x 300 mm
Number of slots
6
Slot 1:
CPU
Slots 2 to 5:
DAU
Slot 6:
Power supply unit
16.1.2 Supply Voltage
Low-voltage version
Direct voltage
Nominal direct supply voltage
DC 24 V / DC 48 V / DC 60 V
Permissible voltage ranges
DC 19.2 V to DC 72 V
High-voltage version
Direct voltage
Nominal direct supply voltage
DC 110 V / DC 125 V / DC 220 V / DC 250 V
Permissible voltage ranges
DC 88 V to DC 300 V
Alternating voltage
(50 Hz / 60 Hz)
Nominal alternating supply voltage
AC 115 V / AC 230 V
Permissible voltage ranges
AC 92 V to AC 276 V
Frequency range
45 Hz to 65 Hz