3 System Messages
285
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
2313
0
OSCOP
Fault during change to normal mode by
OSCOP P
Hotline
2314
2
OSCOP
Lock mode activated by OSCOP
-
2315
0
OSCOP
Fault during change to lock mode by
OSCOP P
Hotline
2316
1
OSCOP
OSCOP P communication request via V20/
V30 protocol rejected
Make sure to use OSCOP P, version 6.60
or higher and set device type
„SIMEAS R-PMU“.
2561
2
OSCOP
Logon service mode
Switching from normal mode to service
mode; possible reason: Firmware update
rejected, parameter or password change
rejected
2562
0
OSCOP
Unable to logon for service mode
Hotline
2563
2
OSCOP
Logoff service mode
-
2564
1
OSCOP
Logoff service mode with device reboot
Switching from normal mode to service
mode; possible reason: Deleting fault
records via OSCOP P, firmware update or
parameter changes
2566
1
OSCOP
Incorrect password
-
3120
2
SYNC
External synchronization pulse OK
-
3121
2
SYNC
Device synchronized
-
3122
0
SYNC
Synchronization fault: Pulse loss
Synchronization signal lost. Check the clock
incl. antenna, antenna cable and the
synchronization signal cable.
3123
1
SYNC
Synchronization: Non-critical pulse failure
Synchronization signal lost for a short time.
Check the clock incl. antenna, antenna
cable and the synchronization signal cable if
this error occurs repeatedly.
3124
0
SYNC
Synchronization fault: Too many non-critical
pulse losses
Synchronization signal lost for a short time
several times. Check the clock incl.
antenna, antenna cable and the
synchronization signal cable.
3125
0
SYNC
Synchronization fault: Pulse width invalid
Pulse width of the synchronization signal
does not meet the specification. Check
parameterization of clock master.
3126
0
SYNC
Synchronization fault: Pulse distance invalid Pulse gap must be 1 s for GPS/DCF77 or
60 s for minute pulse. Check
parameterization of clock master.
3127
0
SYNC
Synchronization fault: DCF77 minute mark
not found
No valid DCF77 signal detected. Check
parameterization of clock master.
3128
0
SYNC
DCF77 synchronization parity fault:
Check clock master and synchronization
signal cable; no valid DCF77 signal
detected.
3129
0
SYNC
Synchronization fault: Non-supported Sync-
Box 7KE6000-8H* connected
The Sync-Box is supported as of SIMEAS
R-PMU firmware V40.01.
3184
2
SYSTEM
DCF77 synchronization-supported
-
3185
1
SYSTEM
Synchronization fault: Manual time setting
rejected
Time setting via OSCOP P is not allowed if
SIMEAS R-PMU is synchronized via GPS
signal.
3186
1
SYSTEM
Manual time setting rejected, minimum
distance not observed
Time gap between two time setting
commands must be at least 4 hours.
3187
1
SYNC
Leap second announcement received
-
3188
1
SYNC
Leap second
-
3189
2
SYNC
System time zone changed
Device time zone was changed due to a
new parameterization or a firmware
upgrade.
Log No.
Type
Class
Description
Comment
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...