1 Product information SIMEAS R
278
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
•
Averaging time power and frequency recorder
The averaging time of the power and frequency recorder must always be < 5 periods.
•
Frequency triggering of the power and frequency recorder
Frequency triggering is only possible when the voltage input signal of a VDAU or VCDAU is
at least 20 V
rms
(applies to both 110 V and 220 V input).
•
Missing entries in the log file on February 28th
If log messages are selected on February 28th of the same day, these messages will not be
transferred. By repeating the selection next day or later the messages will be transferred cor-
rectly.
•
Auto polling in OSCOP P automatic mode
Minimum time between the polling for records must not be less than 5 minutes.
OSCOP P module
Transfer
: Configuration --> Automatic mode --> Sequential control -->
Select device --> General --> Minimum time between intervals.
•
Function "Automatic time setting" in OSCOP P automatic mode (DAKON)
The cycle time of the function "Automatic time setting" must not be less than 20 minutes. Do
not activate this function for SIMEAS R synchronized via a Sync-Box. "Automatic time set-
ting" is only available if OSCOP P runs in DAKON mode.
OSCOP P module Transfer:
Configuration --> Automatic mode --> Synchronization --> Cycle time.
•
ISDN terminal adapter
When using an ISDN terminal adapter connected to SIMEAS R, configure the modem type
as
HAYES
, not as
ISDN
in OSCOP P < V6.60.
Note
No log messages will be lost!
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...