8
8.5 Fault Handling
109
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
8.5
Fault Handling
Evaluate the log recorder (chapter 13) and the device status (chapter 12.1) for fault analysis in
the event of synchronization faults.
During fault handling, a distinction is always made between non-critical and critical
synchronization faults. A non-critical fault is logged, but does not trigger the message
„synchronization malfunction“. A critical fault is logged and simultaneously triggers the message
„synchronization malfunction“.
After the synchronization has failed (LED 13 is OFF or flashing), the SIMEAS R-PMU waits for
a valid synchronization signal. As soon as LED 13 starts flashing, a valid synchronization signal
has been detected. If LED 13 is permanently lits, the measuring system has locked to the
synchronization signal and the device is synchronized.
8.5.1
Minute Pulse
Non-critical fault
Minute pulse failure for one minute
Critical faults
Minute pulse failure for more than one minute
Wrong minute pulse distance
Note
Synchronization adjustment of the measuring system can take up to 45 minutes!
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...