3 System Messages
284
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
1824
0
SYSTEM
Common alarm
A general common alarm occurred.
For further information on this fault, refer to
detailed log entries.
1825
0
SYSTEM
CPU fault
Several possible reasons: DAU and CPU
software version do not match, firmware
update recommended; CPU hardware error;
contact hotline if necessary
1826
1
SYSTEM
Data fault
TAR/TPR record cannot be used due to
inconsistent DAU data. Check via external
or manual trigger if recording is now
possible without errors. LED
Data fault
must
now be off, if not contact hotline.
1827
0
SYSTEM
OSCOP P communication aborted. Fault
no.:
Communication is terminated if there is no
user activity for 10 minutes. Otherwise,
check the communication link.
2049
0
DAU
Invalid link command requested.
Cmd number:
Hotline, install SIMEAS R-PMU firmware or
OSCOP P update
2050
2
DAU
Measurement system time set
Measurement system time was set due to
change of RTC time. Message appears on
device start, too.
2051
1
DAU
Measurement system time could not be set Hotline
2056
2
DAU
Measurement system started
Measurement system was started after a
device start or after the termination of the
service mode.
2057
0
DAU
Unable to start measurement system
Hotline
2058
1
DAU
Measurement system stopped
Measurement system was stopped when
changing to service mode or due to a
hardware fault.
2059
0
DAU
Unable to stop measurement system
Hotline
2064
2
DAU
Recording initiated by manual trigger
-
2065
0
DAU
Recording not initiated by manual trigger
Hotline
2066
2
DAU
Recording initiated by OSCOP P trigger
-
2067
0
DAU
Recording not initiated by OSCOP P trigger Hotline
2068
2
DAU
Recording initiated by external start
-
2069
0
DAU
Recording not initiated by external start
Hotline
2070
2
DAU
Recording terminated by external start
-
2071
0
DAU
Recording not terminated by external start
Hotline
2072
2
DAU
Recording initiated by network trigger
-
2073
0
DAU
Recording not terminated by external start
Hotline
2074
2
DAU
Change to normal mode OK
-
2075
0
DAU
Fault during change to normal mode
Hotline
2076
2
DAU
Change to test mode OK
-
2077
0
DAU
Fault during change to test mode
Hotline
2078
2
DAU
Change to lock mode OK
SIMEAS R-PMU can change to lock mode
automatically or via control panel or via
OSCOP P. Check further log messages for
details.
2079
0
DAU
Fault during change to lock mode
Hotline
2306
0
OSCOP
Login could not be performed
Hotline, install SIMEAS R-PMU firmware or
OSCOP P update
2307
2
OSCOP
RTC set. New time stamp:
RTC was set via OSCOP P.
2310
2
OSCOP
Test mode activated by OSCOP P
-
2311
0
OSCOP
Fault during change to test mode by
OSCOP P
Hotline
2312
2
OSCOP
Normal mode activated by OSCOP P
-
Log No.
Type
Class
Description
Comment
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...