1 Product information SIMEAS R
276
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
A.1
Product information SIMEAS R
Scope of supply
With this consignment you have received one of the following products:
Firmware SIMEAS-R
•
V21.66 for 486-CPU with 16 MB memory
•
V23.16 for 486-CPU with 32 MB memory
•
V30.16 for Elan-CPU
Restrictions
Please notice the following restrictions using SIMEAS R:
•
Compatible OSCOP P versions
This firmware is compatible with OSCOP P V6.40 or higher.
•
Actions needed after firmware update
a) After a firmware update, you have to use the parameterization software OSCOP P to
decrease all memory sizes for the analog fault recorder, the power and frequency recorder,
the mean value writer and for voltage dips by 1 MB.
This action is necessary for an update from
V2.1.64
or lower to
V21.66
, from
V2.3.14
or lower
to
V23.16
and from
V3.0.14
or lower to
V30.16
!
This action is
not
necessary for an update from
V2.1.65
to
V21.66
, from
V2.3.15
to
V23.16
and from
V3.0.15
to
V30.16
!
b) The log system of the current firmware was extended. To allow OSCOP P < V6.60 to dis-
play all log messages in plain text, you have to replace text files in the OSCOP P installation
directory.
Proceed as follows:
Exit OSCOP P. Load the file
OSCOP_P_V6.50_SIMEAS_R_Logs_Patch_1.zip
from the
website http://www.powerquality.de --> Software --> OSCOP P.
Save the file in the OSCOP P installation directory. Uncompress the file. Confirm that the files
Note
To upgrade the SIMEAS R firmware, please refer to the installation instructions
(document number: E50417-X1074-C306-A3).
Note
Decreasing the memory sizes will reorganize the database. The device will then be reset: During
the reset, all data will be deleted in the memory and the memory segments will be created again.
This action will be displayed by blinking LEDs on the front panel.
Do not switch off the SIMEAS R during this activity!
Save all SIMEAS R data before changing the memory sizes.
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...