12
12.11 Slot Description
160
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
12.11.5 DC Channels
The
DC channels
tab is only provided for DDAU modules. This tab is used to parameterize
operational data and information regarding the display of values in OSCOP P.
Figure 12-25 DC channels tab
Select one of the analog channels from the drop-down menu of the
Channel
box.
Enter the
Channel descr.
and
Abbreviation
and select a
Color
.
Select the secondary signal variable that is provided on the input terminals of the DDAU from
the drop-down menu
Meas. input
under
Measurement values
.
Enter the minimum and maximum of the secondary signal variable into the
Min.
and
Max.
boxes.
Use the drop-down menu
Dim.
under
Process values
to select the dimension of the
measured value to be displayed as a y-axis label in the OSCOP P Evaluate module, or enter
a string consisting of maximum six characters. Enter the minimum and maximum of the
converted process variable into the
Min.
and
Max.
boxes.
Note
DDAUs are manufactured for input ranges of DC ±1 V, DC ±10 V or DC ±20 mA. Please check
the type of DDAUs used and make sure you parameterize the input signal variables according
to their intended use.
Note
For DC channels, a mapping for measured values to process signals can be parameterized.
Example: The measurement range DC 0 V to DC +10 V is mapped to the process signals -50 °C
to +100 °C.
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...