16
16.1 Technical Data of the SIMEAS R-PMU
252
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Electromagnetic compatibility
Electromagnetic HF field
amplitude-modulated
IEC 61000-4-3
Test level 3, 10 V/m
80 MHz to 1000 MHz,
80 % amplitude modulation
Electromagnetic HF field
single frequencies
IEC 60255-22-3
Test level 3, 10 V/m
Frequencies:
80 MHz ±0.4 MHz
160 MHz ±0.8 MHz
450 MHz ±2.25 MHz
900 MHz ±5 MHz
80 % amplitude modulation
900 MHz ±5 MHz
50 % pulse modulation
Magnetic field with
power system frequency
IEC 61000-4-8; EN 61000-4-8
Permanent field
Test level 5, 100 A/m
Electrostatic discharge
IEC 61000-4-2; EN 61000-4-2
Contact discharge
Test level 4, test voltage 8 kV
Air discharge
Test level 4, test voltage 15 kV
High frequency, unsymmetrical
amplitude-modulated
IEC 61000-4-6; EN 61000-4-6
Test level 3
Voltage level 10 V
Frequency range 150 kHz to 80 MHz
Fast transients (bursts)
IEC 61000-4-4; EN 61000-4-4
Power supply AC/DC
Test level 4, test voltage 4 kV,
direct coupling
Signal lines, control and
communications lines, data and
Test level 4, test voltage 2 kV,
printer lines
coupling, cap. data link
Repetition frequency
5 kHz
System frequency, unsymmetrical
IEC 60770
Test level 10 V and
Test level 250 V (customer-specific)
1 MHz HF test
IEC 60255-22-1
Power supply, system
and communications lines
Direct and differential-mode voltage 2.5 kV
Signal lines, data and
printer lines
Common-mode voltage 2.5 kV
Differential-mode voltage 1.0 kV
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...