13
13.2 Operator and Error Messages
179
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Signal outputs
Four signal outputs are provided for sending messages to an alarm or telecontrol system.
The first signal output (life contact) is firmly connected to the process monitoring circuit
(watchdog) and signals serious faults that prevent the SIMEAS R-PMU from functioning
properly.
The remaining three outputs can be assigned to any error or status messages. Except for the
first one (watchdog alarm), the signal outputs have been designed as NO contacts. That means
that they are open when the device is OFF.
Messages can be combined to form a group alarm by parameterization. The messages
mentioned in Table 13-1
can be allocated to the relays.
One exception is the live contact that is permanently connected to relay 1 and cannot be
changed.
Live contact
Relay 1 (live contact; fixed assignment) provides information about the device status.
Table 13-4
Preset error and operator messages via relay 2 to 4
Table 13-3
Relay 1 (live contact)
Relay
no.
Message
Remark
1
System OK
Contact open
System malfunction/system OFF
Contact closed
Relay
no.
Message
Remark
2
Device ready for operation
Contact closed
3
Recording active
Contact closed
4
Group alarm
Contact closed
CAUTION
Caution about missing spark suppressor.
Nonobservance of the safety instructions means that moderately
severe or slight injuries can occur.
•
The signal outputs are
not
equipped with a spark suppressor. Appropriate external
protection measures must therefore be ensured if inductive loads are connected.
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...