16
16.1 Technical Data of the SIMEAS R-PMU
251
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
16.1.7
Electrical Tests
Safety regulation
IEC 61010-1; EN 61010-1
Protection class
IEC 61140; EN 61140
Degree of protection
IEC 60529
Flush-mounted housing:
Equipment:
Front IP31
Terminals IP21
(standard
terminal)
Terminals
IP11 (US terminal)
Housing IP20
Operator protection:
IP2x (standard terminal)
IP1x (US terminal)
Surface-mounted housing:
Equipment: Front
IP31
Terminals IP21
Housing IP21
Operator protection:
IP2x
Clearances and creepage distances
IEC 61010-1; EN 61010-1
Overvoltage category
III
Pollution degree
2
Insulation tests
Voltage test
IEC 61010-1; EN 61010-1
(routine test)
Supply voltage
DC 3.1 kV
Voltage/current inputs
3.25 kV, 50 Hz
(VCDAU, VDAU, CDAU)
DC inputs
DC 2.0 kV
Binary inputs and
2.2 kV, 50 Hz
messages
Impulse voltage test
IEC 60255-5
(type test)
1.2/50
μ
s; 0.5 J
Supply voltage and
6 kV
voltage/current inputs
(VCDAU, VDAU, CDAU)
DC inputs, binary inputs
4 kV
and messages
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...