18
18.3 Recording Functions
268
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Transient phasor recorder (TPR)
A fault record that has been recorded contains signal tracks for AC values, phase angles,
symmetrical components, active and reactive power, frequencies, process and binary signals.
General data
Recording rate: 1 to 5 nominal cycles
Resolution of the binary changes: 1 kHz and a maximum of 250 changes per second and
DAU
Recording of the history: up to 30 s at 50 Hz and up to 25 s at 60 Hz before the occurrence
of the fault
Recording time:
via OSCOP P parameterization, 900 s max. at 50 Hz, 750 s max. at 60 Hz
separate setting for manual or logical trigger
in the case of an external triggering at the binary input: for the duration of the pending
external signal (900 s max. at 50 Hz, 750 s max. at 60 Hz)
Recorded values of the DAUs
Note:
Recorded values in {...} are applicable for coupled CDAUs. The current inputs of the
CDAU are coupled to a voltage group, e. g., a VDAU or VCDAU, for power measurement
.
Configurable trigger functions
Level trigger min/max:
Monitoring of the analog measured values for observance of min/max limit values. Triggering
is started as soon as the measured value exceeds or falls below the parameterized limit
value.
Table 18-12 Recorded values of the DAUs
VCDAU
VDAU
CDAU
DDAU
BDAU
V
L
, V
N
, V
ϕ
L
,
ϕ
VN
V
1
, V
2
, V
0
ϕ
1
,
ϕ
2
,
ϕ
0
f
I, I
N
ϕ
L
,
ϕ
IN
I
1
, I
2
, I
0
ϕ
1
,
ϕ
2
,
ϕ
0
f
P
Σ
, Q
Σ
, P, Q
B
V
L
, V
N
, V
ϕ
L
,
ϕ
VN
V
1
, V
2
, V
0
ϕ
1
,
ϕ
2
,
ϕ
0
f
B
I, I
N
ϕ
L
,
ϕ
IN
I
1
, I
2
, I
0
ϕ
1
,
ϕ
2
,
ϕ
0
f
{P
Σ
, Q
Σ
, P, Q}
B
D
B
B
Summary of Contents for SIMEAS R-PMU
Page 22: ...3 22 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 114: ...9 114 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 130: ...11 130 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 260: ...17 260 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...
Page 296: ...Index 296 Digital Fault Recorder SIMEAS R PMU Manual E50417 H1076 C360 A5 Release 10 2012 ...