7.3 Continuous Recorder
100
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
The maximum recording time can be calculated using the following equation:
where:
t
max
= maximum recording time in days
R
= averaging time in seconds
M
= parameterized memory space in megabytes (MByte)
A
= number of VCDAUs activated in the device with star/delta parameterization
B
= number of VCDAUs activated in the device with monophase parameterization plus the
coupled CDAUs with star/delta parameterization
C
= number of CDAUs activated in the device with monophase parameterization
t
max
R M
⋅
A 2,31
⋅
B 4,61
⋅
C 9,23
⋅
+
+
(
)
MByte
----------------------------------------------------------------------------------------------------
=