Process interfacing via an automation system (PLC, PC)
9.1 Integration via PROFINET IO without CM
SIMATIC MV500
152
Operating Instructions, 03/2021, C79000-G8976-C494-05
Assigning PROFINET device names
The optical reader detects the transmission speed of PROFINET automatically. PROFINET
operates in 100 Mbps full duplex mode.
To assign the reader a unique PROFINET device name, follow these steps:
1.
Open the TIA Portal with "Start > All Programs > Siemens Automation > TIA Portal Vxx".
2.
Create a new project.
3.
Change to the Project view.
4.
Using the project tree, insert an S7 controller in the project using the "Add new device"
menu command.
The device view opens and the S7 controller is displayed.
5.
Drag the optical reader from the hardware catalog into the project.
6.
Switch to the network view and connect the reader to the S7 controller.
7.
Optional: Enter a PROFINET device name in the properties of the reader in the tab "General"
> Parameter group "PROFINET interface [X1] > Ethernet add
resses", "PROFINET" area.
8.
Right-click on the reader.