Table 3-14 Pin assignment for digital outputs
Pin
Assignment X7 and X8 (2L+ switched)
View of the cable connector
(wiring side)
1
Not used
2
Output signal DQ
1
: Connector X7
Output signal DQ
3
: Connector X8
3
Supply ground 2M
4
Output signal DQ
0
: Connector X7
Output signal DQ
2
: Connector X8
5
Functional earth FE
;;
IO-Link Master 4 IO‑L 4×M12 (6ES7148-6JD00-0AB0)
The following tables contain the pin assignments for the IO-Link Master 4 IO-L 4×M12.
Pin
Assignment of X1 to X4
View of the cable connector
(wiring side)
1
24 V sensor supply 1U
S
(derived from 1L+ non-switched)
2
24 V actuator supply 2U
A
3
Sensor supply ground 1M
4
IO-Link master
Port 1 (C/Q): Connector X1
Port 2 (C/Q): Connector X2
Port 3 (C/Q): Connector X3
Port 4 (C/Q): Connector X4
5
Actuator supply ground 2M
Port Class A (type A)*
,2/LQN
'HYLFH
;;
Port Class B (type B)
,2/LQN
'HYLFH
;;
* If you use the sockets for IO-Link devices with Port Class A, do not place any signals on pins 2 and 5.
The M12 connectors are designed as Port Class B according to IO-Link specification. Pins 2
and 5 contain an additional power supply.
49
Wiring
3.6 Pin assignment of connectors
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Summary of Contents for SIMATIC ET 200eco PN
Page 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Page 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Page 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...