8.3
Mechanical and climatic environmental conditions
Climatic environmental conditions
Applicable climatic environmental conditions:
Environmental conditions
Fields of application
Remarks
Temperature
from 0 °C to 55 °C
All mounting positions
Temperature change
10 K/h
-
Relative humidity
5 % to max. 100 %
With condensation
Air pressure
From 1140 hPa to 795 hPa
Corresponds to an altitude of -1000 m
to 2000 m
Pollutant concentration
ANSI/ISA-71.04 severity level G1; G2; G3 -
Operating temperature range for the devices
The following devices can be used in different temperature ranges (indoor use only):
Fields of application
Designation
Article number
-25 °C to
55 °C
-25 °C to
60 °C
-40 °C to
60 °C
From product
version
X
X
1
8 DI DC 24V 4×M12
6ES7141-6BF00-0AB0
X
X
X
4
X
X
1
8 DI DC 24V 8×M12
6ES7141-6BG00-0AB0
X
X
X
4
X
X
1
16 DI DC 24V 8×M12
6ES7141-6BH00-0AB0
X
X
X
4
X
X
1
8 DO DC 24V/1,3A 4×M12
6ES7142-6BF00-0AB0
X
X
X
4
X
X
1
8 DO DC 24V/0,5A 4×M12
6ES7142-6BF50-0AB0
X
X
X
4
X
X
1
8 DO DC 24V/1,3A 8×M12
6ES7142-6BG00-0AB0
X
X
X
4
X
X
1
8 DO DC 24V/2,0A 8×M12
6ES7142-6BR00-0AB0
X
X
X
4
X
X
1
16 DO DC 24V/1,3A 8×M12
6ES7142-6BH00-0AB0
X
X
X
4
X
X
1
8 DIO DC 24 V/1,3A 8×M12
6ES7147-6BG00-0AB0
X
X
X
4
X
X
1
8 AI 4 U/I + 4 RTD/TC 8×M12
6ES7144-6KD00-0AB0
X
X
X
4
99
General technical data
8.3 Mechanical and climatic environmental conditions
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Summary of Contents for SIMATIC ET 200eco PN
Page 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Page 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Page 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...