Error class
Error text
Meaning
Remedy
00110
B
6
D
Wire break
•
Signal line to a sensor or actuator inter
rupted
•
Sensor or actuator failure
•
Load impedance too high
•
Correct the process wiring
•
Replace the sensor or actuator
•
Use a sensor with lower impedance
•
Use an actuator with lower load imped
ance
00111
B
7
D
Violation of upper
limit
•
The value is above the overrange
•
Correct the I/O device to sensor tuning
•
Modify measuring range by means of
parameter assignment
01000
B
8
D
Violation of lower
limit
•
Value is below the underrange
•
Correct the I/O device to sensor tuning
•
Modify measuring range by means of
parameter assignment
01001
B
9
D
Error
•
Internal I/O device error has occurred
(diagnostic message on channel 0
applies to the whole I/O device).
•
Replacement of I/O device
10000
B
16
D
Parameter assign
ment errors
•
I/O device is incorrectly parameterized
•
Correct the parameter assignment
10001
B
17
D
1L+ or 2L+ is
missing
•
Supply voltages missing or too low
•
Load voltage supply missing or too low
•
Check the supply voltages
•
Check the load voltage supply
•
Correct the process wiring
10101
B
21
D
Reference chan
nel fault
•
Measurement cable for compensation
interrupted
•
Data record DS2 incorrect
•
Timeout for "Dynamic ref. Temp."
•
Correct the process wiring
•
Check the data record DS2.
•
Send DS2
Error classes for IO-Link Master (6ES7148-6JA00-0AB0), Slot 1
Table 7-9 Overview Error types Slot 1
Error class
Error text
Meaning
IO-Link
Master
IO-Link
Device
00001
B
1
D
Short-circuit
Short circuit at the process cables of the IO-Link device
(0x5151)
X
00010
B
2
D
Undervoltage
Supply voltage too low (0x5110 to 0x5119)
X
00100
B
4
D
Overload
Overload of the output stage of the IO-Link Devices (0x5410)
X
00101
B
5
D
Overtemperature •
Ambient temperature too high (0x4110)
•
IO-Link Device too hot (0x4210)
•
IO temperature exceeded (0x4310)
X
00110
B
6
D
Wire break
•
No IO-Link Device connected
•
Incorrect IO-Link Device connected
•
Signal cable to IO-Link Device interrupted
•
Signal cable to IO-Link Device short-circuited
•
Short-circuit of supply voltage at sensor
•
IO-Link Device addressed with too short communication
cycle time
•
IO-Link Device cannot communicate due to another error
(0xFF10)
X
88
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Interrupt, error, and system messages
7.5 Diagnostics with STEP 7