Technical specifications
Configuration without S7-PCT
supported; autostart function
Data for selection of an IO-Link device
Cable length, unshielded
Max. 20 m
Connection of IO-Link devices
Port type A
Yes; with 3-wire cable
Port type B
Yes; additional device supply: Max. 2 A per Port,
max. 4 A per module
Operating modes
IO-Link
Yes
DI
Yes
DQ
Yes; max. 100 mA
11.2.1
Configuration
Introduction
The IO-Link Master 4 IO-L 4×M12 has four ports. Each port is represented by a submodule.
Configuration of the IO-Link port of the IO-Link Master 4 IO-L 4×M12
You specify the various operating modes of each IO-Link port by configuring a relevant
submodule:
• as digital input by configuring a digital input submodule,
• as digital output by configuring a digital output submodule,
• as IO-Link device by configuring an IO-Link submodule.
• Port deactivated:
– In STEP 7 V5.5 and higher and with GSD: By deleting the submodule,
– in STEP 7 (TIA Portal): By deactivating the port enable.
The IO-Link ports are preconfigured as 2I + PQI.
213
IO-Link Master
11.2 IO-Link Master (6ES7148-6JD00-0AB0)
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN