Properties
The voltage distributor PD DC 24V 1×7/8" 4×M12 has the following properties:
• It distributes the centrally fed supply voltage (7/8") to 4 connectors (M12).
• Integrated electronic short-circuit protection
• Direct connection of up to 4 I/O devices
• Distribution of 1L+ and 2L+
Pin assignment
The tables below show the pin assignments.
Table 12-3 Pin assignment of the 7/8" connector as current input
Pin
Assignment
View of the 7/8" cable connector,
24 V connection
1
Ground 2M (switched)
2
Ground 1M (non-switched)
3
Functional earth FE
4
24 V (1L+ non-switched)
5
24 V (2L+ switched)
;
Table 12-4 Pin assignment of the M12 connector as current output
Pin
Assignment
View of the M12 connection plug (front
view)
1
24 V (1L+ non-switched)
2
Ground 2M (switched)
3
Ground 1M (non-switched)
4
24 V (2L+ switched)
5
Not used
;;