Measurement type
Temperature coefficient
Measuring range
Thermoresistor 4-conductor
Thermoresistor 3-conductor
Thermoresistor 2-conductor
Ni 0.006180
1
/
Ni 0.006720/
Ni 0.005
3
Ni100 Climatic range /
Ni100 Standard range /
Ni120 Climatic range /
Ni120 Standard range /
Ni200 Climatic range /
Ni200 Standard range /
Ni500 Climatic range /
Ni500 Standard range /
Ni1000 Climatic range /
Ni1000 Standard range
1
The default settings for the temperature coefficients apply according to the standard EN60751.
2
This value can also be shown as α = 0.00385055 in the parameter assignment.
3
The thermoresistor LG-Ni1000 corresponds to the thermoresistor Ni1000 with the temperature coeffi
cient 0.005
NOTE
For a thermoresistor, the climatic type is only possible with temperature units Celsius (°C) and
Fahrenheit (°F).
10.1.4
Parameter description analog input
Group diagnostics
You can generally enable and disable the diagnostics function of the device with this
parameter.
The "Fault" and "Parameter assignment error" diagnostics functions are always independent
of the group diagnostics.
Diagnostics: Missing 1L+
If you enable this parameter, the check for missing supply voltage is enabled.
Diagnostics: Short-circuit sensor supply
If you enable this parameter, a diagnostics event is generated if a short-circuit of the sensor
supply to ground is detected and the channel is enabled. The sensor supply is monitored for
connectors X1, X3, X5, and X7. No differentiation is made as to the connector where the
sensor short-circuit occurred.
Interference frequency suppression
With this parameter, you set the integration time of the device, based on the selected
interference frequency. Select the frequency of the supply voltage used. Interference
171
I/O device analog input/analog output
10.1 I/O device analog input
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Summary of Contents for SIMATIC ET 200eco PN
Page 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Page 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Page 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...