Pin assignment
The tables below show the pin assignments.
Pin
Assignment of X05
View of the 7/8" cable connector (24 V con
nection)
1
Ground 2M (switched)
2
Ground 1M (non-switched)
3
Functional earth FE
4
24 V (1L+ non-switched)
5
24 V (2L+ switched)
;
Table 3-26 Pin assignment of the M12 cable connector at the current output
Pin
Assignment of X01 to X04
View of the M12 cable connector
1
24 V (1L+ non-switched)
2
Ground 2M (switched)
3
Ground 1M (non-switched)
4
24 V (2L+ switched)
5
Not used
;;
Information on wiring
• If you are wiring your configuration, you must take into account the impact of cable
length on the supply voltage to the ET 200eco PN (permitted tolerance).
• The maximum input current of the voltage distributor is 8 A for 1L+ non-switched and 2L+
switched.
Do not exceed these values.
CAUTION
Adhering to the maximum infeed currents and cable cross-sections
If you do not adhere to the maximum infeed currents and the cable cross-sections
required for these currents, you will risk overheating the cable insulation and contacts
resulting in damage to the device.
61
Wiring
3.8 Wiring the voltage distributor
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN