2.2
Installation with mounting rail
Version
The mounting rail is available with a length of 500 mm.
Installing the mounting rail
Cut the 500-mm rail to suit your requirements and drill mounting holes for the M8 screws.
You should distribute the mounting holes evenly at a pitch of 182 mm on the rail, starting at
a distance of 12 mm from the edge.
Use the rack screw to bolt the I/O devices onto the mounting rail.
Figure 2-4 Installing the mounting rail
2.3
Mounting position, mounting dimensions
Mounting position
The ET 200eco PN can be mounted in any position.
Mounting and clearance dimensions
Table 2-1 Mounting dimensions
Dimensions
single width
double width
Mounting width
30 mm
60 mm
Mounting height
200 mm
175 mm
Mounting depth
49 mm
49 mm
24
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Installing
2.3 Mounting position, mounting dimensions