Technical specifications
Supported Ethernet services
PROFINET IO (Device)
•
ping
•
arp
•
LLDP
•
Network diagnostics (SNMP)
•
DCP
•
Prioritized startup
•
Media redundancy
PROFINET interface
•
Connection socket
2 x M12 d-coded
•
Switch function
Yes, internal
•
Auto-crossover
Yes; if autonegotiation is enabled
Manufacturer ID (Vendor ID)
002A
H
Device ID (DeviceID)
0306
H
Voltages and currents
Supply voltage 1L+
DC 24 V
Reverse polarity protection
Yes; against destruction
•
Infeed current 1L+
Max. 4 A
Supply voltage 2L+
DC 24 V
•
Infeed current 2L+
Max. 4 A
Current consumption
•
From supply voltage 1L+
Typ. 110 mA
•
From supply voltage 2L+
0 mA
Power loss of the device
Typ. 2.8 W, without sensor current
Analog inputs
Number of inputs
8 (4 for U or I, 4 for RTD or thermocouple)
Cable length, shielded
Max. 30 m
Sensor supply
Number of sensor supplies
4
Total current
Max. 1 A
Short-circuit protection
Yes; electronic, for each module, to ground
•
Response threshold
Min. 1.4 A
Sensor selection data
Input ranges (Rated value)/input resistance or input voltage
•
Voltage
±80 mV/10 MΩ
±10 V/100 kΩ
0 to 10 V/100 kΩ
1 to 5 V/100 kΩ
154
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device analog input/analog output
10.1 I/O device analog input
Summary of Contents for SIMATIC ET 200eco PN
Page 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Page 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Page 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...