Technical data
Parallel wiring of two outputs
•
To increase performance
No
•
For redundant control of a load
Supported
Controlling of a digital input
Yes
Switching frequency
•
With resistive load
Max. 100 Hz
•
With inductive load
Max. 0.5 Hz
•
With lamp load
Max. 1 Hz
Limiting of the inductive shutdown voltage to lamp
load
Typ. 1L+/2L+ (-47 V)
Short-circuit protection of the output
Yes, electronic
•
Response threshold
Typ. 1.8 A (per channel)
11.1.1
Parameters for IO-Link Master
Parameters for the IO-Link Master 4 IO-L + 8 DI + 4 DO DC 24V/1,3A 8×M12
Parameters
Range of values
Default setting
Range of effectiveness
Slot 1 "4 IO-L"
Group diagnostics
•
Disable
•
Enable
Disable
Slot 1
Diagnostics enable for Ports 1
•
Disable
•
Enable
Disable
Channel
Diagnostics enable for Port 2
•
Disable
•
Enable
Disable
Channel
Diagnostics enable for Port 3
•
Disable
•
Enable
Disable
Channel
Diagnostics enable for Port 4
•
Disable
•
Enable
Disable
Channel
Slot 2 "8 DI + 4 DO DC 24V/1,3A 8×M12"
Group diagnostics
•
Disable
•
Enable
Disable
Slot 2
Diagnostics: Missing 2L+
•
Disable
•
Enable
Disable
Channel group
Response to CPU/Master STOP
•
Shut down
•
Retain last value
Shut down
Slot 2
Inputs
Diagnostics: Short-circuit of the
sensor supply to M
•
Disable
•
Enable
Disable
Channel group*
Channel 4
Diagnostics: Wire break
•
Disable
•
Enable
Disable
Channel
206
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
IO-Link Master
11.1 IO-Link Master (6ES7148-6JA00-0AB0)
Summary of Contents for SIMATIC ET 200eco PN
Page 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Page 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Page 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...