9.3.2
Parameter overview digital inputs/digital outputs
Parameters for 8 DIO DC 24V/1,3A 8×M12 (6ES7147-6BG00-0AB0)
Parameters
Range of values
Default setting
Range of effectiveness
Group diagnostics
•
Disable
•
Enable
Disable
Device
Diagnostics: Missing 1L+ or 2L+
•
Disable
•
Enable
Disable
Channel group
Diagnostics: Wire break at inputs 0 to 7
(channels 0 to 7)
•
Disable
•
Enable
Disable
Channel
Diagnostics: Short-circuit to M,
inputs 0 to 7
•
Disable
•
Enable
Disable
Channel
Response to CPU/Master STOP
•
Shut down
•
Retain last value
Shut down
Device
Diagnostics: Wire break outputs 0 to 7
•
Disable
•
Enable
Disable
Channel
Diagnostics: Short-circuit to M,
outputs 0 to 7
•
Disable
•
Enable
Disable
Channel
Freely parameterizable
•
Digital input
•
Digital output
Digital input
Channel
149
I/O device digital inputs/digital outputs
9.3 I/O device digital inputs/digital outputs
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Summary of Contents for SIMATIC ET 200eco PN