Technical specifications
Ambient temperature
positive
negative
(0 °C to
-25 °C)
negative
(-25 °C to
-40 °C)
U
0.1%
0.15%
0.3%
Operational limit (across the temperature range,
relative to output range)
I
0.15%
0.25%
0.4%
U
0.08%
Basic error limit (operational limit at 25°C, relative
to output range)
I
0.1%
Ambient temperature
positive
negative
U
0.001%/K
0.003%/K
Temperature error (relative to output range)
I
0.0025%/K
0.005%/K
Linearity error (relative to output range)
± 0.02%
Repeat accuracy (in steady-state condition at 25°C,
relative to output range)
±0.008%
U
±0.6 mVrms
Output ripple (relative to output range, bandwidth
0 to 50 kHz
I
±0.4 nArms
Status, interrupts, diagnostics
Interrupts
Yes
Diagnostics functions
•
Group error/maintenance
Red/yellow "SF/MT" LED
•
Bus monitoring PROFINET IO
Red "BF" LED
•
Monitoring of supply voltage 1L+
Green "ON" LED
•
Existing connection to network
Green "P1 LK" and "P2 LK" LED; LED for PROFINET
IO infeed and loop-through
•
Fault at analog output
Red LED
•
Diagnostic information can be read
Yes
Monitoring for
•
Supply voltage 1L+
Yes
•
Sensor supply short-circuit
Yes
•
Short-circuit
Yes; channel (voltage)
•
Wire break
Yes; channel (current)
•
Thermal overload at output
Yes; channel
Insulation
Insulation test voltage
•
Ethernet interface
1500 V
rms
(IEEE802.3, Type Test)
•
All other circuit elements
707 V DC (type test)
Electrical isolation
•
Between 1L+ and 2L+
Yes
193
I/O device analog input/analog output
10.2 I/O device analog output
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Summary of Contents for SIMATIC ET 200eco PN
Page 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Page 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Page 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...