Technical data
•
Between Ethernet and all other circuit elements Yes
Status, interrupts, diagnostics
Interrupts
Yes
Diagnostics function
Yes
•
Group error/maintenance
Red/yellow "SF/MT" LED
•
Bus monitoring PROFINET IO
Red "BF" LED
•
Monitoring of supply voltage 1L+
Green "ON" LED
•
Monitoring of supply voltage 2L+
Green "DC24V" LED
•
Existing connection to network
Green "P1 LK" and "P2 LK" LED; LED for PROFINET IO
infeed and loop-through
•
Digital output
Green LED
•
Fault at digital output
Red LED
•
Diagnostic information can be read
Yes
Monitoring for
•
Failure of 1L+ and 2L+
Yes
•
Short-circuit
Yes, per channel
•
Wire break
Yes, in the off state, per channel
Actuator selection data
Cable length, shielded
Max. 30 m
Cable length, unshielded
Max. 30 m
Output voltage
•
Nominal value
DC 24 V
•
For signal "1"
Min. 1L+/2L+ (-0.8 V)
Output current
•
At signal "1"
2.0 A
•
For "0" signal (residual current)
Max. 1.5 mA
Load resistance range
12 Ω to 3.3 kΩ
Lamp load
Max. 10 W
Parallel wiring of two outputs
•
To increase performance
No
•
For redundant control of a load
Supported
Control of a digital input
Yes
Switching frequency
•
With resistive load
Max. 100 Hz
•
With inductive load
Max. 0.5 Hz
•
With lamp load
Max. 1 Hz
Limiting of the inductive shutdown voltage to lamp
load
Typ. 1L+/2L+ (-47 V)
137
I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Summary of Contents for SIMATIC ET 200eco PN
Page 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Page 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Page 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...