Technical specifications
•
Between 1L+, channels and all other circuit ele
ments
No
•
Between channels
No
•
Between Ethernet and all other circuit elements Yes
See also
Response times for analog input device and output device (Page 259)
10.2.2
Parameter overview analog output
Parameters for analog output 4 AO U/I 4xM12 (6ES7145-6HD00-0AB0)
Parameters
Range of values
Default setting
Range of effective
ness
Group diagnostics
•
Disable
•
Enable
Disable
Device
Diagnostics, missing 1L+
•
Disable
•
Enable
Disable
Device
Diagnostics, sensor supply
short-circuit
•
Disable
•
Enable
Disable
Device
Response to CPU/Master
STOP
•
Output has no current or
voltage
•
Retain last value
•
Switch to substitute val
ues
Output has no current
or voltage
Device
Type of output
•
Disabled
•
Voltage
•
Current
Voltage
Channel
Output range
•
1 to 5 V
•
0 to 10 V
•
±10 V
•
0 to 20 mA
•
4 to 20 mA
•
±20 mA
±10 V
Channel
Diagnostics, wire break at
outputs
•
Disable
•
Enable
Disable
Channel
Diagnostics, short-circuit at
outputs
•
Disable
•
Enable
Disable
Channel
Diagnostics, overload
•
Disable
•
Enable
Disable
Channel
Substitute value
Each value in the nominal
range, overrange, and
underrange
0
Channel
194
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
I/O device analog input/analog output
10.2 I/O device analog output