Technical specifications
Interference suppression, error limits
Interference suppression for
f = n x (f1 ± 0.5%), (f1 = interference frequency)
46 dB
•
Common-mode interference (interference
voltage < 5 V)
70 dB
•
Series-mode interference (peak value of inter
ference < Rated value of input range)
46 dB
Crosstalk between inputs
< -85 dB
Ambient temperature
positive
negative
(0 °C to
-25 °C)
negative
(-25 °C to
-40 °C)
R, RTD
0.1%
0.15%
0.3%
Operational limit (across temperature range, relat
ive to input range)
TC
0.2%
0.25%
0.4%
R, RTD
0.05%
Basic error limit (operational limit at 25 °C, relative
to input range)
3
TC
0.1%
Ambient temperature
positive
negative
R, RTD
0.0005%/K
0.001%/K
Temperature error (relative to input range)
TC
0.0035%/K
0.007%/K
Linearity error (relative to input range)
±0.01%
Repeat accuracy (in steady-state condition at 25°C,
relative to input range)
±0.008%
Operational limits (relative to internal temperature
sensor)
±3 °C
Basic error limits (relative to internal temperature
sensor)
±2 °C
Status, interrupts, diagnostics
Interrupts
Yes
Diagnostics functions
•
Group error/maintenance
Red/yellow "SF/MT" LED
•
Bus monitoring PROFINET IO
Red "BF" LED
•
Monitoring of supply voltage 1L+
Green "ON" LED
•
Existing connection to bus
Green "P1 LK" and "P2 LK" LED; LED for PROFINET IO
infeed and loop-through
•
Analog input error
Red LED
•
Diagnostic information can be read
Yes
Monitoring for
•
Wire break
Resistors and thermoresistors
•
Underflow and overflow
Yes
•
Supply voltage 1L+
Yes
165
I/O device analog input/analog output
10.1 I/O device analog input
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Summary of Contents for SIMATIC ET 200eco PN
Page 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Page 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Page 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...