Current measuring range: 4 to 20 mA
Units
Measuring range
4 to 20 mA
Decimal
Hexadecimal
Range
> 22.81 mA
32767
7FFF
H
Overflow
22.81 mA
32511
7EFF
H
27649
6C01
H
Overrange
20 mA
27648
6C00
H
16 mA
20736
5100
H
4 mA + 578.7 nA
1
0001
H
4 mA
0
0000
H
Nominal range
1
FFFF
H
1.185 mA
-4864
ED00
H
Underrange
< 1.185 mA
32767
7FFF
H
Wire break
-32768
8000
H
Underflow
Measuring range for current: ±20 mA
Units
Measuring range ±20 mA
Decimal
Hexadecimal
Range
> 23.52 mA
32767
7FFF
H
Overflow
23.52 mA
32511
7EFF
H
27649
6C01
H
Overrange
20 mA
27648
6C00
H
15 mA
20736
5100
H
723.4 nA
1
0001
H
0 mA
0
0000
H
-1
FFFF
H
-15 mA
-20736
AF00
H
-20 mA
-27648
9400
H
Nominal range
-27649
93FF
H
-23.52 mA
-32512
8100
H
Underrange
< -23.52 mA
-32768
8000
H
Underflow
179
I/O device analog input/analog output
10.1 I/O device analog input
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Summary of Contents for SIMATIC ET 200eco PN
Page 233: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 234 Dimensional drawings C ...
Page 265: ...266 ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN Open Source Software ...
Page 278: ...ET 200eco PN Operating Instructions 06 2022 A5E01250250 AN 279 Y Y cable 37 Index ...