![Siemens IM 153-4 PN Operating Instructions Manual Download Page 188](http://html.mh-extra.com/html/siemens/im-153-4-pn/im-153-4-pn_operating-instructions-manual_377175188.webp)
Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
186
Operating Instructions, 12/2008, EWA-4NEB780600602-08
LEDs
SF
BF
ON
Meaning
Remedy
on
off
on
inadmissible PROFIBUS address
Is the SF LED of an SM / FM also lit?
•
If so: Error or diagnosis in an S7 300
module
•
If not: IM 153-1 is faulty.
On the IM 153-1 set a valid PROFIBUS address (1
to 125)
Check the SM / FM with the diagnostics. Replace
the S7-300 module or the IM 153-1 or contact your
Siemens representative.
off
off
on
There is data exchange between the DP
master and the ET 200M.
The preset configuration and actual
configuration of the ET 200M match.
—
* not relevant
Status and error displays of the IM 153-2
6)
%)
21
6)
%)
$&7
$&7
21
,0$$$%
,0%[
6)
%)
$&7
21
,0%[[
%)
216XSSO\YROWDJH*UHHQ
DYDLODEOH
$&70RGXOHDFWLYH<HOORZ
RQO\LQUHGXQGDQWPRGH
%)b(UURURQWKHXQGHUODLGEXV5HG
LUUHOHYDQWIRU(70
%)%)(UURURQWKH352),%86'35HG
6)*URXSHUURU5HG
Table 9- 2
LEDs
SF
BF /
BF1
ACT
ON
Meaning
Remedy
off
off
off
off
No voltage on the IM 153-2 or there is a
hardware fault with the IM 153-2.
Switch on the power supply module or
replace the IM 153-2.
*
*
*
on
There is voltage on the IM 153-2.
IM 153-2 is functioning.
—
on
off
off
off
IM 153-2 is undergoing a hardware reset
after switching on
—
on
on
on
on
Hardware test after switching on
—
on
on
off
off
The operating system update is running
—
off
flashes
at
0.5 Hz
off
off
The operating system update has
concluded successfully
with IM 153-2Bx00:
remove the SIMATIC Micro Memory
card and switch off the IM 153-2.
on
flashes
at
0.5 Hz
off
off
external error, e.g. unsuitable operating
system or SIMATIC Micro Memory card
Use a suitable operating system for the
update.
Do not remove the SIMATIC Micro
Memory card during the update (only
with IM 153-2Bx00).
on
flashes
at
2 Hz
off
off
internal error, e.g. when writing the update
files
Repeat the update process.
If the LEDs indicate an error, the
internal memory is faulty.
Summary of Contents for IM 153-4 PN