Commissioning
6.2 PROFINET IO
ET 200M
100
Operating Instructions, 12/2008, EWA-4NEB780600602-08
6.2.4
Configuring ports of the IM 153-4 PN
Introduction
The IM 153-4 PN interface module can diagnose both of its ports: X1 P1 and X1 P2.
Requirement
●
The ports must be configured in HW Config.
●
The port diagnostics must be released.
Configuring ports in HW Config
Configure both ports of the IM 153-4 PN in HW Config in the "Properties of the IM 153-4 PN
port..." dialog:
●
Addresses tab:
Specify the diagnostic address of each port.
●
Topology tab:
Specify a "Port interconnection".
●
Options tab:
To enable the port diagnostics, select the following for "Connection" under "Transmission
Medium / Duplex": "Automatic Settings (monitor)".
Reference
See
STEP 7 Online Help.