7SR11 & 7SR12 Performance Specification
©2017 Siemens Protection Devices Limited
Chapter 3 Page 39 of 56
2.14 51N Time Delayed Derived Earth Fault
2.14.1
Reference
Parameter
Value
Is
Setting
0.05, 0.6… 2.5
xIn
char
Characteristic setting
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
Tm
Time Multiplier setting
IEC: 0.025, 0.030… 1.6
ANSI: 0.025, 0.030… 1.6 1.7… 5, 6… 15
t
d
Delay setting
0, 0.01… 20 s
t
res
Reset setting
ANSI DECAYING, 0, 1… 60 s
I
Applied Current
(for operate time)
IDMTL
2 to 20 x Is
DTL
5 x Is
2.14.2
Operate and Reset Level
Attribute
Value
I
op
Operate level
105 %
Is
,
±
4 % or
±
1%
In
Reset level
≥
95 %
I
op
Repeatability
±
1 %
Variation
-10 °C to +55 °C
≤
5 %
f
nom
± 5 %
≤
5 %
2.14.3
Operate and Reset Time
Attribute
Value
Starter operate time (
≥
2
xIs
)
30 ms,
±
20ms
t
op
Operate time
char
= IEC-NI,
IEC-VI,
IEC-EI,
IEC-LTI
[ ]
Tm
K
t
Is
I
op
×
−
=
1
α
,
±
5 % absolute or
±
30 ms,
for char = IEC-NI : K = 0.14,
α
= 0.02
IEC-VI : K = 13.5,
α
= 1.0
IEC-EI : K = 80.0,
α
= 2.0
IEC-LTI : K = 120.0,
α
= 1.0
char
= ANSI-MI,
ANSI-VI,
ANSI-EI
[ ]
Tm
B
A
t
P
Is
I
op
×
+
−
=
1
,
±
5 % absolute or
±
30 ms,
(ANSI-EI +5% -10 % absolute for I/Is>10 with TMS >2)
for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02
ANSI-VI : A = 19.61, B = 0.491, P = 2.0
ANSI-EI : A = 28.2,
B = 0.1217, P = 2.0
char
= DTL
t
d
,
±
1 % or
±
20ms
Reset time
ANSI DECAYING
[ ]
Tm
R
t
Is
I
res
×
−
=
1
2
,
±
5 % absolute or
±
30 ms,
for char = ANSI-MI : R = 4.85
ANSI-VI : R = 21.6
ANSI-EI : R = 29.1
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......