7SR11 & 7SR12 Applications Guide
©2017 Siemens Protection Devices Limited
Chapter 7 Page 7 of 48
If additional pickup or drop-off time delays are required by the scheme logic, this functionality can be achieved by
programmable logic within the device.
Example.
An AC oprated Binary input is required to inhibit the 50-1 protection element with 100ms minimum pickup delay
and 200ms minimum drop-off delay.
1) Set Binary Input 1 for AC operation:
2) Set quicklogic equation E1 to operate from Binary Input 1 and apply required delays:
3) Set equation E1 to operate virtual I/O V1 in the Output Matrix:
4) Set virtual I/O V1 to operate Inhibit 51-1 in the Input Matrix:
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......