7SR11 & 7SR12 Description Of Operation
©2017 Siemens Protection Devices Limited Chapter 1 Page 73 of 88
Section 5: Supervision Functions
5.1 Circuit Breaker Failure (50BF)
The circuit breaker fail function has two time delayed outputs that can be used for combinations of re-tripping or
back-tripping. CB Fail outputs are given after elapse of the
50BF-1 Delay
or
50BF-2 Delay
settings. The two
timers run concurrently.
The circuit breaker fail protection time delays are initiated either from:
An output
Trip Contact
of the relay (MENU: OUTPUT CONFIG\TRIP CONFIG\Trip Contacts), or
A binary or virtual input assigned to
50BF Ext Trig
(MENU: INPUT CONFIG\INPUT MATRIX\50BF Ext
Trig).
A binary or virtual input assigned to
50BF Mech Trip
(MENU: INPUT CONFIG\INPUT MATRIX\
50BF
Mech Trip).
CB Fail outputs will be issued providing any of the 3 phase currents are above the
50BF Setting
or the current in
the fourth CT is above
50BF-I4
for longer than the
50BF-n Delay
setting, or for a mechanical protection trip the
circuit breaker is still closed when the
50BF-n Delay
setting has expired – indicating that the fault has not been
cleared.
Both
50BF-1
and
50BF-2
can be mapped to any output contact or LED.
An output is also given to indicate the faulted phase,
50BF PhA
,
50BF PhB, 50BF PhC and 50BF EF
If the
CB Faulty
input (MENU: INPUT CONFIG\INPUT MATRIX\CB Faulty) is energised when a CB trip is given
the time delays
50BF-n Delay
will be by-passed and the output given immediately.
Operation of the CB Fail elements can be inhibited from:
Inhibit 50BF
A binary or virtual input.
Trip Contact
50BF-1
50BF-2
≥
1
IL1
>
50BF Setting
50BF Element
Enabled
Disabled
50BF-1 Delay
50BF-2 Delay
Inhibit 50BF
&
&
50BF Ext Trig
IL3
IL2
&
50BF CB Faulty
≥
1
≥
1
CB Closed
≥
1
50BF Mech Trip
&
IL4
>
50BF-I4 Setting
≥
1
&
&
&
Figure 5-1 Logic Diagram: Circuit Breaker Fail Protection (50BF)
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......