7SR11 & 7SR12 Performance Specification
©2017 Siemens Protection Devices Limited
Chapter 3 Page 51 of 56
2.23 81 Under/over frequency
2.23.1
Reference
Parameter
Value
Fs
Setting
43, 43.01… 68 Hz
V
s
Guard
Guard Setting
35, 35.5, …199.5, 200 V
Hyst
Hysteresis setting
0, 0.1… 2%
td
Delay setting
0.00, 0.01… 20.0, 20.1… 100.0, 101.…1000, 1010 … 10000 ,
10100 … 14400 s
2.23.2
Operate and Reset Level
Attribute
Value
F
op
Operate level
100 %
F
s
,
±
10mHz
Reset level
overfrequency
(100 % -
hyst
)
xF
op,
±
10mHz
underfrequency
(100 % +
hyst
)
xF
op,
±
10mHz
Repeatability
±
1 %
Variation
-10 °C to +55 °C
≤
5 %
2.23.3
Operate and Reset Time
Attribute
Value
t
basic
Element basic
operate time
(for ROCOF
between 1 and
5.0 Hz/sec)
overfrequency
Typically
<
110ms
Maximum
<
150ms
underfrequency
Typically
<
110ms
Maximum
<
150ms
Element basic
operate time
(for ROCOF
between 0.1
and 1.0 Hz/sec)
overfrequency
Typically
<
150ms
Maximum
<
200ms
underfrequency
Typically
<
150ms
Maximum
<
200ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
Disengaging time
<
100 ms
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......