Chapter 4 - 7SR120 · Data Communications Definitions
© 2017 Siemens Protection Devices Limited
Chapter 4 - Page 53 of 84
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
(unsol. resp)
22
7
32-Bit Delta Counter
Change Event (with Time)
22
8
16-Bit Delta Counter
Change Event (with Time)
23
0
Frozen Counter Event
(Variation 0 is used to
request default variation)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
23
1 (default -
see note 1)
32-Bit Frozen
Counter Event
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
17, 28 (index)
23
2
16-Bit Frozen
Counter Event
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
17, 28 (index)
23
3
32-Bit Frozen Delta
Counter Event
23
4
16-Bit Frozen Delta
Counter Event
23
5
32-Bit Frozen Counter
Event (with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
23
6
32-Bit Frozen Counter
Event (with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
23
7
32-Bit Frozen Delta Counter
Event (with Time)
23
8
16-Bit Frozen Delta Counter
Event (with Time)
30
0
Analog Input
- Any Variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30
1
32-Bit Analog Input
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
2 (default -
see note 1)
16-Bit Analog Input
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
3
32-Bit Analog Input
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
4
16-Bit Analog Input
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
5
short floating point
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
6
long floating point
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
31
0
Frozen Analog Input
- Any Variation
31
1
32-Bit Frozen Analog Input
31
2
16-Bit Frozen Analog Input
31
3
32-Bit Frozen Analog Input
(with Time of freeze)
31
4
16-Bit Frozen Analog Input
(with Time of freeze)
31
5
32-Bit Frozen Analog Input
(without Flag)
31
6
16-Bit Frozen Analog Input
(without Flag)
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......