7SR11 & 7SR12 Performance Specification
©2017 Siemens Protection Devices Limited
Chapter 3 Page 45 of 56
2.18 55 Power Factor
2.18.1
Reference
Parameter
Value
PF
s
55-n Setting
0.05…0.99
t
d
55-n Delay setting
0.00 … 14400 s
2.18.2
Operate and Reset Level
Attribute
Value
PF
op
Operate Level
PF
s
±
0.05
Reset Level
Under PF
≤
PF
op
+ 0.02
Over PF
≥
PF
op
-
0.02
Repeatability
±
0.05
Variation
-10 °C to +55 °C
±
0.05
f
nom
– 3 Hz to
f
nom
+ 2 Hz
±
0.05
2.18.3
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
≤
70 ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Disengaging time
< 80 ms
2.18.4
Operate Threshold
Attribute
Value
Minimum levels for
operation
I
2.5 % In
V
2.5% Vn
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......