7SR11 & 7SR12 Description Of Operation
©2017 Siemens Protection Devices Limited Chapter 1 Page 9 of 88
Table 1-1
7SR11 Ordering Options
Product description Variants
Order No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Nondirectional O/C Relay (Argus)
7 S R 1 1 0
□
-
□ □
A
□ □
-
□ □
A 0
Overcurrent and earth fault
Protection relay
Protection Product
Overcurrent – Non Directional
1
Housing I/O and Fascia
1 CT, 3 Binary Inputs / 5 Binary Outputs, 10 LEDs
1 1
C
4 CT, 3 Binary Inputs / 5 Binary Outputs, 10 LEDs
2 A/C/D
4 CT, 6 Binary Inputs / 8 Binary Outputs, 10 LEDs
3 C/D
4 CT, 4 Binary Inputs / 8 Binary Outputs, 10 LEDs
8)
7 C/D
Measuring Input
1/5 A, 50/60Hz
1)
1 A/C/D
1/5 A, 50/60Hz with SEF Input
2)
3 C/D
Auxiliary voltage
PSU Rated: 80-250V DC / 115V AC
6)
. Binary input threshold 19V DC (Rated: 24-250V DC / 115V AC) G
PSU Rated: 80-250V DC. Binary input threshold 88V DC (Rated: 110-250V DC)
H
PSU Rated: 24-60V DC. Binary input threshold 19V DC (Rated: 24-250V DC)
J
PSU Rated: 24-250V DC / 100-230V AC. BI threshold 19V DC (Rated: 24-250V DC / 100-120V AC)
M
PSU Rated: 24-250V DC / 100-230V AC. BI threshold 88V DC (Rated: 110-250V DC)
N
Communication Interface
Standard version – included in all models, USB front port, RS485 rear port (E4 Case)
1 2
Standard version – plus additional rear electrical Ethernet RJ45 (x2), E6 Case
7)
7 7 C/D
Standard version – plus additional rear optical Ethernet duplex (x2), E6 Case
7 )
8 7 C/D
Protocol
IEC 60870-5-103 Modbus RTU and DNP3 (user selectable)
2
IEC 60870-5-103 Modbus RTU, DNP3 and IEC 61850 (user selectable settings)
7)
7
Relay Cover
Standard Version – No Push Buttons
1
Push Buttons – Down and Right Arrows
2
Protection Function Packages
Basic version
5)
A
46BC
3)
Broken conductor/load unbalance
50
3)
Instantaneous phase fault overcurrent
50BF
3)
Circuit breaker fail
50G/50N
Instantaneous earth fault
51
3)
Time delayed phase fault overcurrent
51G/51N Time delayed earth fault
60CTS
3)
CT Supervision
64H
High impedance REF
74T&C Trip & Close circuit supervision
86 Hand reset contacts
Standard version
C
37
Undercurrent
46BC
3)
Broken conductor/load unbalance
46NPS
3)
Negative phase sequence overcurrent
49
3)
Thermal overload
50
3)
Instantaneous phase fault overcurrent
50AFD
Arc Flash Detection
50BF
3)
Circuit breaker fail
50G/50N Instantaneous earth fault
50SEF
2)
Instantaneous sensitive earth fault
51
3)
Time delayed phase fault overcurrent
51G/51N
Time delayed earth fault
51SEF
2)
Time delayed sensitive earth fault
60CT
3)
CT Supervision
64H High Impedance REF
74T/CC
Trip and Close circuit supervision
81HBL2
4)
2
nd
harmonic block/inrush restraint
51C
3)
Cold load pickup
86 Hand reset contacts
Programmable logic
(continued on next page)
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......