4.1.2
Auto-Reclose Example 2, simpler multishot sequence
Requirement: Settings shall provide one phase fault reclose for IDMTL overcurrent protection but should lockout
for DTL highset- and two recloses for earth fault protection but only 1 for the EF DTL highest.
Proposed settings include:
CONTROL & LOGIC > AUTORECLOSE PROT’N:
79 P/F Inst Trips: none
79 E/F Inst Trips: none
79 P/F Delayed Trips: 51-1
(50-1 is used for Hiset but does not start ARC)
79 E/F Delayed Trips: 51N-1, 50N-1
79 P/F HS Trips: none
79 E/F HS Trips: 50N-1
CONTROL & LOGIC > AUTORECLOSE CONFIG
79 Num Shots: 2
(required for E/F)
CONTROL & LOGIC > AUTORECLOSE CONFIG > P/F SHOTS
79 P/F Prot’n Trip 1 : Inst
(not important as there are no Inst elements set)
79 P/F Prot’n Trip 2 : Delayed
(not important as there are no Inst elements set)
79 P/F Prot’n Trip 3 : Delayed
(not used as only 1 P/F reclose is executed)
79 P/F HS Trips to Lockout : 5
(not used)
79 P/F Delayed Trips to Lockout : 2
(prevents a 2
nd
P/F reclose)
CONTROL & LOGIC > AUTORECLOSE CONFIG > E/F SHOTS
79 E/F Prot’n Trip 1 : Delayed
(not important as there are no Inst elements set)
79 E/F Prot’n Trip 2 : Delayed
(not important as there are no Inst elements set)
79 E/F Prot’n Trip 3 : Delayed
(not important as there are no Inst elements set)
79 E/F Prot’n Trip 4 : Delayed
(not used as only 2 E/F reclose are ever executed)
79 E/F HS Trips to Lockout : 2
(must be >1 but not used due to Numshots =2)
79 E/F Delayed Trips to Lockout : 5
(must be >2 but not used due to Numshots =2)
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......