7SR11 & 7SR12 Performance Specification
©2017 Siemens Protection Devices Limited
Chapter 3 Page 52 of 56
Section 3: Supervision Functions
3.1
46BC Broken Conductor
3.1.1
Reference
Parameter
Value
NPS to PPS ratio
20,21…100%
t
f
Delay setting
0.03,04,20.0,20.1,100,101,1000,1010…..14400 s
3.1.2
Operate and Reset Level
Attribute
Value
I
curr
Operate level
100 %
I
set
±
5 %
Reset level
90 %
I
curr ,
±
5 %
Repeatability
±
1 %
Variation
-10 °C to +55 °C
≤
5 %
f
nom
± 5 %
harmonics to
f
cutoff
≤
5 %
3.1.3
Operate and Reset Time
Attribute
Value
t
basic
Basic operate time 1x In to 0 A
40 ms
Operate time
t
f
+
t
basic
,
±
1 % or
±
20ms
Repeatability
±
1 % or
±
20ms
Variation
f
nom
± 5 %
harmonics to
f
cutoff
≤
5 %
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......