7SR11 & 7SR12 Performance Specification
©2017 Siemens Protection Devices Limited
Chapter 3 Page 43 of 56
2.16 51V Voltage Controlled Overcurrent
2.16.1
Reference
Parameter
Value
Vs
Setting
60V
m
multiplier
0.5
Is
Setting
1xIn
2.16.2
Operate and Reset Level
Attribute
Value
V
op
Operate level
100 %
Vs
,
±
1 % or ± 0.25V
Reset level
≤
105 %
V
op
Repeatability
±
1 %
Variation
-10 °C to +55 °C
≤
5 %
f
nom
± 5 %
harmonics to
f
cutoff
≤
5 %
Operate and Reset Time
As per Phase Fault Shaped Characteristic Element (ANSI 51).
Where Pickup Level = Is for Voltage > Vs
Pickup Level = (Is x m) for Voltage < Vs
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......