7SR11 & 7SR12 Performance Specification
©2017 Siemens Protection Devices Limited
Chapter 3 Page 56 of 56
3.5
74TCS & 74CCS Trip & Close Circuit Supervision
3.5.1
Reference
Parameter
Value
t
d
Delay setting
0, 0.02…60 s
3.5.2
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
30ms
±
10ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
Variation
-10 °C to +55 °C
≤
5 %
f
nom
± 5 %
≤
5 %
3.6
81HBL2 Inrush Detector
3.6.1
Reference
Parameter
Value
I
Setting
(Ratio of 2nd Harmonic current to
Fundamental component current)
0.10, 0.11... 0.5
3.6.2
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
Will pick-up before operation of any protection element due
to magnetic inrush
Reset Time
Will operate until drop-off of any protection element due to
magnetic inrush
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......