7SR120 Technical Manual
Chapter 4 - Page 54 of 84
© 2017 Siemens Protection Devices Limited
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
32
0
Analog Change Event
- Any Variation)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
32
1
32Bit-Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
2
16Bit-Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
3
32Bit-Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
4 (default -
see note 1)
16Bit-Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
5
short floating point
Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
6
long floating point
Analog Change Event
(without Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
7
short floating point
Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
32
8
long floating point
Analog Change Event
(with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
33
0
Frozen Analog Event
- Any Variation
33
1
32-Bit Frozen Analog Event
(without Time)
33
2
16-Bit Frozen Analog Event
(without Time)
33
3
32-Bit Frozen Analog Event
(with Time)
33
4
16-Bit Frozen Analog Event
(with Time)
33
5
Short Floating Point
Frozen Analog Event
33
6
Long Floating Point
Frozen Analog Event
33
7
Extended Floating Point
Frozen Analog Event
34
0
Analog Input Deadband
(Variation 0 is used to
request default variation)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
34
1
16 bit Analog
Input Deadband
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
34
2 (default -
see note 1)
32 bit Analog
Input Deadband
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
34
3
Short Floating Point
Analog Input Deadband
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......