7SR11 & 7SR12 Description Of Operation
©2017 Siemens Protection Devices Limited Chapter 1 Page 47 of 88
3.5 Current Protection: High Impedance Restricted Earth
Fault - (64H)
One high impedance Restricted Earth Fault (REF) element is provided
64H-1
.
The relay utilises fundamental current measurement values for this function.
The single phase current input is derived from the residual output of line/neutral CTs connected in parallel. An
external stabilising resistor must be connected in series with this input to ensure that this element provides a high
impedance path.
64H Current Setting
sets the pick-up current level. An output is given after elapse of the
64H Delay
setting.
External components – a series stabilising resistor and a non-linear resistor – are used with this function. See
‘Applications Guide’ for advice in specifying suitable component values.
Operation of the high impedance element can be inhibited from:
Inhibit 64H
A binary or virtual input.
64H
>
c
64H Current Setting
64H Delay
c
Inhibit 64H
64H Element
Enabled
Disabled
&
I
4
(I
g
or I
SEF
)
Figure 3-16 Logic Diagram: High Impedance REF (64H)
3.6 Current Protection: Cold Load (51c)
The setting of each shaped overcurrent element (51-n) can be inhibited and alternative ‘cold load’ settings (51c-n)
can be applied for a period following circuit switch in.
The Cold Load settings are applied after the circuit breaker has been open for longer than the
Pick-Up Time
setting.
Following circuit breaker closure the ‘cold load’ overcurrent settings will revert to those defined in the Phase
Overcurrent menu (51-n) after either elapse of the
Drop-Off Time
setting or when the measured current falls
below the
Reduced Current Level
setting for a time in excess of
Reduced Current Time
setting.
During cold load settings conditions any directional settings applied in the Phase Overcurrent menu are still
applicable.
A CB ‘Don’t Believe It’ (DBI) alarm condition, see Section 4.3, is not acted on, causing the element to remain
operating in accordance with the relevant 51-n settings. Where the
Reduced Current
setting is set to
OFF
reversion to 51-n settings will only occur at the end of the
Drop-Off Time
. If any element is picked up on expiry of
Drop-Off Time
the relay will issue a trip (and lockout if a recloser is present).
If the circuit breaker is re-opened before expiry of the
Drop-Off Time
the drop-off timer is held but not reset.
Resetting the timer for each trip could result in damaging levels of current flowing for a prolonged period during a
rapid sequence of trips/closes.
Cold load trips use the same binary output(s) as the associated 51-n element.
Operation of the cold load element can be inhibited from:
Inhibit Cold Load
A binary or virtual input.
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......