7SR11 & 7SR12 Description Of Operation
©2017 Siemens Protection Devices Limited Chapter 1 Page 63 of 88
The dead time is initiated when the trip output contact reset, the pickup is reset and the CB is open.
The CB close output relay is energised after the dead time has elapsed.
Figure 4-1 Typical AR Sequence with 3 Inst and 1 Delayed trip
4.1.3
A
UTORECLOSE
P
ROT
’
N
M
ENU
This menu presents the Overcurrent Protection elements available for each type of Fault i.e. P/F, E/F (N/G) or
SEF and allows the user to select those that are to be applied as
Inst trips
; those that are to be applied as
Delayed Trips
; and those that are to be applied as
HS Trips
(HighSet), as required by the selected sequence.
There is no corresponding setting for External as the External protection type is not normally controlled by the
Auto Reclose Relay. The resultant configuration enables the Auto Reclose function to correctly apply the required
Protection for each shot in a sequence.
4.1.4
A
UTORECLOSE
C
ONFIG
M
ENU
This menu allows the following settings to be made:-
79 Autoreclose
Enabled
turns ON all AutoReclose Functions.
79 Num Shots
Sets the allowed number of AutoReclose attempts in a sequence.
79 Retry Enable
Enabled
configures the relay to perform further attempts to automatically Close the
Circuit Breaker where the CB has initially failed to close in response to a Close
command. If the first attempt fails the relay will wait for the
79 Retry Interval
to expire
then attempt to Close the CB again.
79 Retry Attempts
Sets the maximum number of retry attempts.
79 Retry Interval
Sets the time delay between retry attempts.
79 Reclose Blocked
Delay
If the CB is not ready to receive a Close command or if system conditions are such
that the CB should not be closed immediately e.g. a close-spring is not charged, then
a Binary input mapped to
Reclose Block
can be raised and the Close pulse will not be
issued but will be held-back. The
79 Reclose Blocked Delay
sets the time
Reclose
Block
is allowed to be raised, if this time delay expires the Relay will go to Lockout. If
Reclose Block is cleared, before this time expires, then the CB Close pulse will be
issued at that point in time. Dead Time + Reclose Blocked Delay = Lockout.
79 Sequence Fail Timer
Sets the time that AutoReclose start can be primed. Where this time expires before all
the DAR start signals are not received i.e. the CB has opened, protection pickups have
reset and the trip relay has reset, the Relay goes to Lockout.
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......